High power condensing gas boilers Genus Premium EVO HP are ideal for systems that require high power and suitable for domestic and non-domestic applications.Available for single installation or batch installation. Maximum comfort with the confidence of high-performance condensing technology. The product is able to adjust its power to maintain the temperature at the desired level.
Advantages:
- Up to 6 boilers in line installation and up to 8 boilers in back to back installation.
- LCD multifunction display.
- The boiler is only for heating but its equipment allows the production of domestic hot water gas by connecting an external tank.
- Primary stainless steel heat exchanger.
- High efficiency continuous configuration pump.

AUTO function: Maximum comfort, efficiency and energy savings, based on the automatic analysis of the environmental conditions, the internal devices connected and the required efficiency. It thus avoids temperature fluctuations and peaks, giving a constant temperature for maximum thermal comfort.
Even more energy saving is guaranteed thanks to the two speed pump (only for 85-100 kW) or full modulating pump (for 85-100-115-150 kW) , available as optional accessories.
Additional advantages:
- 108% efficiency (****) with an energy saving up to 35%
- Compatible with the Sensys Net control unit and with devices that use the BusBridge Net communication protocol in individual installation.
- BusBridgeNet communication protocol
- Super quiet
- It can be connected to an external accumulator
Technical Data Genus Premium EVO HP:
|
45FF
|
65FF
|
85FF
|
100FF
|
115FF
|
150FF
|
Power specifications
|
Max/Min nominal calorific flow rate (Ηi)
|
Kw
|
41/12,2
|
58/17,4
|
80/20
|
88,3/22,1
|
109/27,3
|
140/35
|
Max/Min nominal calorific flow rate (Ηs)
|
Kw
|
45,6/13,6
|
64,4/19,3
|
88,9/22,2
|
98,1/24,6
|
121,1/30,3
|
155,6/38,9
|
Max/min power output (60/80°C)
|
%
|
97/96,1
|
98,8/99,4
|
97,5/98,4
|
97,5/98,4
|
97,5/98,4
|
97,3/98,4
|
Max/min power output (30/50°C)
|
%
|
106,4/107,5
|
107,4/109,5
|
105,6/108,1
|
106,5/108,1
|
106,2/108,4
|
106,1/108,3
|
Max/min power output (30/40°C)
|
106,5/107,7
|
108,2/110
|
106,1/108,3
|
107/108,3
|
107,7/108,6
|
107,1/108,7
|
Max/min useful thermal power (80°C-60°C) (Heating system)
|
%
|
39,7/11,7
|
57,3/17,3
|
78,0/19,7
|
86,1/21,7
|
106,3/26,9
|
136,2/34,4
|
Max/min useful thermal power (50°C-30°C) (Heating system)
|
%
|
43,6/13,1
|
62,3/19,1
|
84,5/21,6
|
94,0/23,9
|
115,8/29,6
|
148,5/38,
|
Max/min useful thermal power (40°C-30°C)
|
43,7/13,1
|
62,8/19,3
|
84,9/21,7
|
94,5/23,9
|
117,1/29,6
|
150,1/38
|
Combustion efficiency (of flue gas)
|
%
|
97,3
|
97,32
|
97,3
|
97,3
|
96,8
|
96,9
|
Efficiency at 30% at 30°C
|
%
|
107,4
|
109,8
|
108,1
|
108,1
|
108,3
|
108,5
|
Efficiency at 30% at 47°C
|
%
|
104,8
|
105,3
|
104,9
|
104,9
|
102,5
|
103
|
Efficiency rating (dir. 94/42/EEC)
|
****
|
Loss of burner gas when operating
|
%
|
2,8
|
3,2
|
3,1
|
Απώλειες σε στάση (ΔΤ=50°C)
|
%
|
0,24
|
0,25
|
0,25
|
<0,15
|
<0,15
|
Heating circuit
|
Μax/Min heating pressure
|
bar
|
4/0,7
|
6/0,7
|
6/0,7
|
6/0,7
|
6/0,7
|
Max/min heating temperature (high temperature range)
|
°C
|
82/35
|
85/35
|
Max/min heating temperature (low temperature range)
|
°C
|
45/20
|
Domestic hot water
|
Max/Min Domestic Hot water temperature
|
°C
|
60/40
|